Clearance/Spacing

Card Set Information

Author:
djwaite
ID:
11199
Filename:
Clearance/Spacing
Updated:
2010-03-18 22:46:20
Tags:
SCE
Folders:

Description:
work
Show Answers:

Home > Flashcards > Print Preview

The flashcards below were created by user djwaite on FreezingBlue Flashcards. What would you like to do?


  1. Min. clearance for open wire service drops over any pool is?
    20'R from edges and 20' from highest water level

    (ESR 2)
  2. Min. clearance for Triplex service drop over a swimming pool is?
    • 16' for a commercial or public pool
    • 12' for a private pool

    (ESR 2)
  3. Min. clearance of a residential service at the weather head?
    10'

    (ESR 2)
  4. Min. clearance of a residential service in a roadway?
    16' at the curb and 18' twelve feet from the curb.

    (ESR 2)
  5. Min. clearance for a commercial service drop at weather head?
    12' min

    (ESR 2)
  6. MIN. distance from bottom of transformer to center of top skate?
    10"

    (DOH-ap124)