BFD Hydraulics

Card Set Information

Author:
stevevizz
ID:
221848
Filename:
BFD Hydraulics
Updated:
2014-07-23 17:19:24
Tags:
BFD
Folders:

Description:
Bakersfield Fire Dept. Hydraulics
Show Answers:

Home > Flashcards > Print Preview

The flashcards below were created by user stevevizz on FreezingBlue Flashcards. What would you like to do?


  1. Master Stream
    1 1/4"
    415
  2. Master Stream
    1 3/8"
    502
  3. Master Stream
    1 1/2"
    597
  4. Master Stream
    1 5/8"
    701
  5. Master Stream
    1 3/4"
    813
  6. Master Stream
    2"
    1062
  7. Hand Held Smooth Bore
    15/16"
    180
  8. Hand Held Smooth Bore
    1"
    210
  9. Hand Held Smooth Bore
    1 1/8"
    265
  10. Hand Held Smooth Bore
    1 1/4"
    328
  11. E.P.( Elevation Pressure)=
    .5 x H
  12. F.L.=
    C (Q)2L
  13. % Drop
    (Static - Residual)100/ Static
  14. C - 1"
    150
  15. C - 1 1/2"
    24
  16. C - 1 3/4"
    15.5
  17. C - 2 1/2"
    2
  18. C - 3"
    .8
  19. C - 3 1/2"
    .4
  20. C - 4"
    .2
  21. Siamese Co
    2 - 2 1/2"
    .5
  22. Siamese Co
    3 - 2 1/2"
    .22
  23. Siamese Co.
    1- 3", 1- 2 1/2"
    .3
  24. Siamese Co
    1- 3", 2- 2 1/2"
    .16
  25. Portable Monitors
    25 psi
  26. Standpipe
    25 psi + back pressure
  27. Ladder Pipe
    80 psi
  28. Pump Capacity 
    150 psi
    100%
  29. Pump Capacity
    200 psi
    70%
  30. Pump Capacity
    250 psi
    50%
  31. Pressure Drop
    0-10
    3x
  32. Pressure Drop
    11-15
    2x
  33. Prssure Drop
    16-25
    1x
  34. Pressure Drop
    25+
    May support additional lines
  35. E.P. Booster lines at 30 gpm
    130 psi
  36. Sprinkler Connection
    • 150 psi
    • 125 psi for older systems
  37. When pumping to a supply line or relay use an inlet pressure of?
    20 psi

What would you like to do?

Home > Flashcards > Print Preview