  1. S/R Hi Flux Trip Setpoint
    >= 10^5 CPS
  2. I/R Hi Flux Trip Setpoint
    IR=25% PR
  3. P/R Hi Flux "Low" Setpoint
    >= 25%
  4. P/R Hi Flux "Hi" Setpoint
    109%
  5. Power Range Hi Positive Rate Setpoint
    +5% w/ time constant of 2 seconds
  6. Manual Trip Setpoint
    None, handswitches
  7. RCP Undervoltage Setpoint
    4830 Volts
  8. RCP Underfrequency
    57.2 HZ
  9. Low Loop Flow Setpoint
    <=90% flow 1 loop if P-8 met, 2 loops if P-7 met but less than p-8
  10. OT N-16 setpoint
    115% +- Penalties
  11. OP N-16 Setpoint
    112%
  12. Pzr Low Pressure Setpoint
    1880 PSIG
  13. Pzr Hi Pressure Setpoint
    2385 PSIG
  14. Pzr Hi LVL
    92%
  15. S/G Lo-Lo LVL setpoint
    U1 38% U2 35.4%
  16. Turbine Trip Setpoint
    <= 72.3 PSIG trip oil pressure and stop valves closed
  17. Safety Injection Setpoint
    Any SI signal initiates Rx Trip
  18. SSPS General Warning
    Loss of 2/2 SSPS trains
  19. List of Rx Trips
    S/R, I/R, P/R Hi Flux, Power Range Hi Positive Rate, Manual, RCP under voltage & under frequency, low loop flow, OT N16, OP N16 Pzr Low press, Pzr Hi Press, Pzr Hi Lvl, S/G LO Lo lvl, Turbine Trip, SI, SSPS warning 