    • 1. The trainee must successfully complete ?
    • 5 hour of training
  1. DRY VACUUM TEST ...what is needed to pass?
    pump can lose no more than ten (10) inches of Mercury in one minute to pass
  2. PREPARATION FOR QUICK LIFT AND FURTHER TESTING
    • Attach stream straightener and water choke valve to front 2 ½" discharge on panel side
    • Attach (2) 100' 2 ½" hoses to far side outlets
    • Attach (1) 50' 2 ½" hose to panel (1250 GPM
    • Attach (2) 50' 2 ½" hoses to panel (1500 GPM
    • Attach proper tip to collector nozzle (as found on chart
  3. QUICK LIFT TEST
    Water should attain pressure in a maximum of 30 seconds for?
    1250 GPM pump or 45 seconds for 1500 GPM pump
  4. 100% CAPACITY TEST......... Testing gauges must read
    • 150 PSI pump pressure at 100% capacity
    • 100 PSI nozzle pressure per chart
    • Set timer for 20 minutes and start

    • NOTE: When adjusting RPM to obtain proper nozzle and pump pressure, closing line valves will increase pump pressure and decrease nozzle pressure
    • NOTE: Any time engine temperature exceeds manufacturer’s recommended maximum temperature, start cool down procedures. Discontinue test if temperature exceeds maximum temperature by 10Ε Fahrenheit
  5. 10% OVERLOAD TEST
    • With all valves set at 100% capacity test specifications, attempt to pump 165 PSI pump pressure
    • NOTE: This is an acceptance requirement only. It shows the condition of the pump
  6. 70% CAPACITY TEST
    • Increase RPM to 200 PSI pump pressure
    • Set timer for 10 minutes
  7. 50% CAPACITY TEST
    • Procedures are the same as 70% Capacity test, but to 50% specifications
    • Tip is same size as for 70% Capacity test
    • Set timer for 10 minutes
  8. RELIEF VALVE TEST
    • Use (2) 2 ½" discharges fully open
    • Set throttle and relief valve at 150 PSI
    • Pressure should not increase more than 30 PSI
    • This is a pass / fail test