-
What is differential protection?
Differential protection will operate when it has determined that the difference between the current going into the transformer and coming out of the transformer has exceeded a pre-determined amount.
-
What is the advantage of using differential protection over simpleover-current protection to protect transformers?
The differentially connected over-current relay should not operate on either an external fault or normal load (designed to operate only on an internal fault)
-
What is the limitation of using over-current relays to employdifferential protection?
Overcurrent relays must be set above any error current that could flow(ex. saturated CTs)on an external fault. This reduces sensitivity.
-
How do percentage differential relays increase the sensitivity ofdifferential protection?
- Sophisticated percentage differential relays improve sensitivity without affecting security
- -improves ability to to detect low-magnitude internal faults
- -employs operate and restraint coils
-
How can magnetizing inrush current pose a problem to differentialprotection?
- -Magnetizing inrush current has a high harmonic content and is especially rich in second harmonic
- -This magnetizing current appears to a differential relay as an internal fault as it does not flow out the other side of the transformer
- -The more sophisticated relays are designed to block tripping if the second harmonic content exceeds a certain amount.
-
How are a gas relay’s alarm and trip outputs triggered?
- Alarm
- – Faults of minor nature cause a slow accumulation of gas, gas displaces oil in the relay chamber, which at a certain point operates a micro-switch
- Trip
- – A major internal fault will vaporize oil and and cause a rapid build-up of pressure, causing a pressure wave that will operate a micro-switch
-
What two conditions in combination will trigger “bullet-hole”protection?
- The combination of the low oil alarm and the gas accumulation alarm provide indication of loss of oil
- -these alarm contacts are connected in series
-
How does a winding temperature device measure temperature? Whatis it used for?
- This device has a heater which is fed from a CT in the transformer winding, thus, temperature measured by the thermometer depends on top oil temperature and the current in the transformer winding
- It initiates alarms, cooling and tripping
-
How are faults cleared on substation transformers without high-sidecircuit breakers?
Either a transfer trip is sent to the remote line terminal or a SOG is applied to force operation of remote line terminal protection
-
What is transformer auto isolation?
- After a Circuit Breaker tripping to clear a fault, the transformer disconnect switches are automatically opened to isolate the transformer.
- Closing of these disconnects is blocked until the lockout is reset (Block Close)
-
What type of relay is generally used in bus protection?
Over-current relays
-
How must the phase and neutral relays of bus protection be set interms of coordination?
- -The phase relays (A,B,C) must be set above the maximum load current and must coordinate with feeder phase over-current relays
- -The Neutral relay must be set above the maximum neutral current and must coordinate with feeder neutral relays
-
What is the purpose of torque control and how does it function?
- Differentiates between Fault Current and High Load Current by monitoring for an acceptable voltage
- -Torque control ensures that bus protection does not operate on load current
- -used on distribution buses that must supply many feeders and significant load
- Under-voltage/distance elements are added to work in coordination with feeder bus over-current relays to ensure that the proper protection operates first
-
What is the risk in using the under-voltage method of torque control?
Loss of voltage to the under-voltage relay may cause bus protection misoperation
-
Why would a distance relay be used to provide torque control?
- In stations where the feeder reactor is located on the source side, most of the voltage drop will be across the reactor for a bus fault.
- This means there may be insufficient voltage to operate an under-voltage relay
- In this case, a distance relay is used to detect the bus fault and provide torque control
-
What is the risk in using the distance method of torque control?
Loss of voltage to the distance relay will prevent bus protection operation for a bus phase fault
-
Describe typical substation feeder relaying.
- Feeder relaying consists of four over-current relays (One for each phase and a neutral)
- -usually contain an inverse time over-current and instantaneous overcurrent element
- -Instantaneous elements must be set with large enough margins to avoid misoperation
- -Feeder relays are set to coordinate with downstream reclosers and fuses
-
How is a feeder fault cleared if the feeder circuit breaker fails tooperate?
- Bus Protection would then operate to remove the fault.
- This would result in multiple feeders out.
- OO 1T-29B describes the policy for restoring a Main Feeder Bus
-
How does a fused cutout function?
- The hinged portion of the door is held closed by a replacable fuse link.
- When there is fault current, the fuse melts and the door swings open by spring action and gravity
-
What is an expulsion fuse?
Expulsion fuses are cutout fuses that when melted, expel the arc byproducts from the fuse tube
-
How does the fault protection provided by vista switchgear differ fromthat of a switching kiosk?
- In a vista, the ‘fault interrupter way’ operates in series with a vacuum fault interrupter (there are no replacable fuses and is 3 phase ganged)
- In a Kiosk, the fuses are replaced and are single pole switched
-
How are the majority of dead-front transformers protected?
They are protected by a series combination of a replacable expulsion fuse and a back-up current limiting fuse
-
Can a bay-o-net fuse be used to break load in an LPT?
Although the manufacturer says bay-o-net fuses can break load, it is not a BCHydro practice
-
How are shunt capacitor banks primarily protected? What benefitsdoes this provide?
- Individual capacitor fuses, which protect the individual units
- -maintains service continuity, removing only a failed can
- -prevents damage to adjacent capacitors and equipment
- -provides visual indication of a failed unit
-
What means of protection can be provided to isolate a shunt capacitorbank from the system in the event of a major fault?
Phase fuses or phase and ground over-current relays may be used between the system and capacitor bank
-
Why is neutral-shift over-voltage protection applied to shunt capacitorbanks?
- The neutral potential will be permanently shifted proportionate to the change in impedance of the leg of the failed unit
- If the shift exceeds a predetermined threshold, breaker tripping is initiated
|
|