Pump Chart

Card Set Information

Author:
mac519
ID:
308393
Filename:
Pump Chart
Updated:
2015-09-23 15:39:09
Tags:
nozzle pressure friction loss
Folders:

Description:
Flashcards based on the information on the pump chart
Show Answers:

Home > Flashcards > Print Preview

The flashcards below were created by user mac519 on FreezingBlue Flashcards. What would you like to do?


  1. 1-3/4" TFT (low pressure) NP
    55
  2. 1-3/4" TFT (low pressure) GPM
    175
  3. 1-3/4" TFT (standard pressure) NP
    100
  4. 1-3/4" TFT (standard pressure) GPM
    200
  5. 2-1/2" TFT (automatic nozzle) NP
    100
  6. 2-1/2" TFT (automatic nozzle) GPM
    325
  7. Master Stream TFT (automatic) NP
    100
  8. Master Stream TFT (automatic) GPM
    1000
  9. 1" Straight Tip Handline NP
    50
  10. 1" Straight Tip Handline GPM
    200
  11. 1-1/8" Straight Tip Handline NP
    50
  12. 1-1/8" Straight Tip Handline GPM
    250
  13. 1-1/4" Straight Tip Handline NP
    50
  14. 1-1/4" Straight Tip Handline GPM
    325
  15. 1-3/8" Straight Tip Master Stream NP
    80
  16. 1-3/8" Straight Tip Master Stream GPM
    500
  17. 1-1/2" Straight Tip Master Stream NP
    80
  18. 1-1/2" Straight Tip Master Stream GPM
    600
  19. 1-3/4" Straight Tip Master Stream NP
    80
  20. 1-3/4" Straight Tip Master Stream GPM
    800
  21. 2" Straight Tip Master Stream NP
    80
  22. 2" Straight Tip Master Stream GPM
    1000
  23. 2-1/4" Straight Tip Master Stream NP
    80
  24. 2-1/4" Straight Tip Master Stream GPM
    1350
  25. 2-1/2" Straight Tip Master Stream NP
    80
  26. 2-1/2" Straight Tip Master Stream GPM
    1650
  27. 1-1/2" Brenson Nozzle (cellar nozzle) NP
    50
  28. 1-1/2" Brenson Nozzle (cellar nozzle) GPM
    100
  29. Relay Engine (@ next engine) NP
    50
  30. Foam Eductor (PSI @ Eductor) NP
    200
  31. Foam Eductor (PSI @ Eductor) GPM
    100
  32. Sprinkler/Standpipe Connection NP
    150
  33. BlitzFire TFT Low Pressure Nozzle NP
    55
  34. BlitzFire TFT Low Pressure Nozzle GPM
    500
  35. BlitzFire TFT High Pressure Nozzle NP
    100
  36. BlitzFire TFT High Pressure Nozzle GPM
    500
  37. Formula for estimating needed fire flow
    (Length x Width) / 3 x percentage of involvment per floor
  38. Friction Loss per 100 ft of 1-3/4" @ 175 gpm
    47
  39. Friction Loss per 100 ft of 2-1/2" @ 325 gpm
    21
  40. Friction Loss per 100 ft of 2-1/2" @ 200 gpm
    8
  41. Friction Loss per 100 ft of 2-1/2" @ 250 gpm
    13
  42. Friction Loss per 100 ft of 3" @ 500 gpm
    20
  43. Friction Loss per 100 ft of 3" @ 600 gpm
    29
  44. Friction Loss per 100 ft of 3" @ 800 gpm
    51
  45. Friction Loss per 100 ft of 5" @ 1000 gpm
    8
  46. Friction Loss per 100 ft of 5" @ 1350 gpm
    15
  47. Friction Loss per 100 ft of 5" @ 1650 gpm
    21
  48. Friction Loss for standard appliance
    10 psi
  49. Friction Loss for Master Stream (Mounted)
    20 psi
  50. Friction Loss for Master Stream (remote base)
    45 psi
  51. Friction Loss for Ladder 61 waterway (rear)
    90 psi
  52. Friction Loss for Ladder 65 waterway (rear)
    75 psi
  53. Friction Loss for BlitzFire Base (@500 gpm w/TFT)
    22 psi
  54. Pressure loss for elevation (+/- psi per 10ft)
    5 psi

What would you like to do?

Home > Flashcards > Print Preview